Page 7 - Submittal Form - For Sizing

SPECIFICATIONS SPM-15 / SPM-30 / SPM-65 / SPM-135
CAPACITIES:
15, 30, 65,
and 135 GPH.
PRESSURE:
Maximum operating pressure to 80 PSI or 200’ of head.
MOTORS:
All motors are 60 HERTZ, 1725 RPM, continuous duty.
1/6, 1/4, 1/3
HP: SPLIT PHASE, 115 OR 230 VOLT operation
1/2
HP: Capacitor start / induction run, TEFC, DUAL 115/230 VOLT
Motors are clockwise as viewed from motor shaft end.
50
HERTZ and/or 3 PHASE motors are available upon request.
PUMPS:
SPM 15, 35, AND 65 USES WEBSTER “2R” SERIES PUMP UNITS
SPM 135 USES WEBSTER “2V” SERIES PUMP UNITS
WEBSTER 2R AND 2V ARE UL LISTED
PORTING:
SPM 15, 30, 65: 1/4” NPTF - 2 INLETS, OUTLETPORTANDTOPAND BOTTOMRETURNS
SPM 135: 1/4” NPTF - OUTLET PORT
3/8”
NPTF - RETURN PORT, 2 OPTIONAL INLETS
1/2”
NPTF - INLET
SEAL:
All models - Double lip type. BUNA N. VITON available upon request.
MOUNTING:
All models - Four bolt foot mount.
FILTER:
Rotary self cleaning type, except in SPM 135. Use of external line filter recommended.
For additional filter requirements, contact the factory.
VALVES:
Pressure regulating assembly in pump maintains set pressure.
Check valve maintains oil in feeder lines for instant starts.
External regulators are required for flow rates higher than 135 GPH. Contact the factory
for information.
GAUGE:
2 1/2”
DIA., Calibrated from 30” of HG vacuum to 100 PSI.
For other requirements, contact the factory.
INLET VACUUM:
All units - 15” HG maximum.
NATIONAL FIRE PROTECTION ASSOCIATION COMPLIANCE REQUIRES
FUEL INLET PRESSURE NOT TO EXCEED 3 PSIG.
CONTROLS:
Duplex automatic with lead-lag switch, alarm, and push button test switch.
Duplex manual with selector switch only.
Additional controls are available. Contact the factory.
7
L002715:Layout 1 10/24/07 1:02 PM Page 7