Page 12 - Submittal Form - For Sizing

MOTOR HORSEPOWER (1725 RPM STANDARD)
No.
Description
25
.25
HP
33
.33
HP
50
.50
HP
75
.75
HP
100
1.0
HP
150
1.5
HP
200
2.0
HP
300
3.0
HP
= only available in 115V or 230V single phase
MOTOR HORSEPOWER (1725 RPM STANDARD)
Under pressure, read
horsepower required at 1750 RPM
Maximum
Pump
gph
25
100
200
300
Model
Nominal
psi
psi
psi
psiI
18
BR
82
.25
.25
.25
.33
37
BR
159
.25
.25
.50
.75
47
BR
220
.25
.50
.75
1.00
59
BR
292
.25
.50
.75
1.50
SPMB Duplex Ordering Code
When ordering SPMB Duplex models add suffix:
DM,” for manual control models, or “DA,” for
automatic control models.
Example: SPMB-50AT/18BR-DA
Code
Duplex Units
DM
Duplex with manual controls
DA
Duplex with automatic controls
MOTOR PHASE
Code
Description
A Single Phase / 60 cycle / 115/208/230 VAC
B Three Phase / 60 cycle / 208 / 230 / 460 VAC
X Consult factory for other types
MOTOR ENCLOSURE
Code
Description
T
TEFC Std/ thru 2 HP
O
OPDP Std. over 2 HP
SPMB Ordering Code
SPMB 50 A T 18BR DM
1
1
2
3
4
5
2
3
4
5
When sizing SPMB units, remember that the pressures indi-
cated are at the pump outlet.
All pumps relying on atmospheric pressure to push the fuel oil
into them are subject to cavitation. As fuel viscosity (thick-
ness) increases, the tendency for cavitation becomes greater.
Therefore, iti is best to mount the pump at the base of the
tank and to use the largest diameter, shortest length, and
straightest inlet possible.
A large diameter inlet pipe or hose necked-down at the pump
is preferable to a longer lentth of similar diameter pipe be-
cause the fuel tends to adhere to the inside of the pipe.
When initially starting a unit, it is desireable and sometimes
necessary to have a vent valve or plug on the pressure side
of the pump to facilitate its priming.
*
*
*
12