Page 11 - Submittal Form - For Sizing

SPECIFICATIONS SPMB 18B-R / 37B-R / 47B-R / 59B-R
CAPACITIES:
82, 159, 220,
and 292 GPH.
PRESSURE:
Maximum operating pressure to 80 PSI or 200’ of head.
MOTORS:
All motors are 60 HERTZ, 1725 RPM, continuous duty.
SPLIT PHASE, 115 OR 230 VOLT operation
1/2
HP: Capacitor start / induction run, TEFC, DUAL 115/230 VOLT
Motors are clockwise as viewed from motor shaft end.
50
HERTZ and/or 3 PHASE motors are available upon request.
PUMPS:
18
B-R, 37B-R, 47B-R, 59B-R
PORTING:
18
B, 37B, 47B 1/2” NPTF side inlet and outlet
59
B 3/4” NPTF side inlet and outlet
SEAL:
All models - Double lip type. VITON
MOUNTING:
All models - Four bolt foot mount.
FILTER:
Use of external line filter recommended.
VALVES:
External pressure regulating or relief valve recommended.
GAUGE:
2 1/2”
DIA., Calibrated from 30” of HG vacuum to 100 PSI.
INLET VACUUM:
All units - 15” HG maximum.
NATIONAL FIRE PROTECTION ASSOCIATION COMPLIANCE REQUIRES
FUEL INLET PRESSURE NOT TO EXCEED 3 PSIG.
CONTROLS:
Duplex automatic with lead-lag switch, alarm, and push button test switch.
Duplex manual with selector switch only.
Additional controls are available. Contact the factory.
11