Page 3 - Bio Pump M Series

Specifications
Dimensions
Firing Capacity:
Recommended to 3 GPH fire size for
pressures from 100 to 150 PSI with
#1, #2
fuel oil, Kerosene, or Bio Fuel
B100-B5 Bio Diesel
Gear Capacity:
25
GPH @ 100-150 PSI with #1, #2
fuel oil, Kerosene, or Bio Fuel. B100-
B5 Bio Diesel.
Pressure:
Factory set at 100 PSI.
Adjustable to 150 PSI.
Inlet Requirements:
10”
Hg maximum vacuum (approx.
10’
vertical lift - exact distance will
vary with tubing diameter and length).
3
psig maximum inlet pressure.
Speed:
3450
RPM.
Rotation:
(
As viewed from shaft end):
Clockwise (D Style).
Porting:
• 1/8”
NPTF, side located nozzle port.
• 1/8”
NPTF, top located gauge port.
• 1/4”
NPTF, bottom and cover
located inlet ports and bottom
located return port.
Bypass plug accessible through the
side located bleed port plug
assembly.
• 3/8”
flow through bleed valve.
Nozzle Location:
(
As viewed from shaft end):
Clockwise (D Style) - Right side.
Shaft:
5/16”
dia., 1.65” extension from
mounting face, with keyless “D” drive.
Filter:
Self-cleaning rotary type.
Elastomers:
VITON shaft seal.
All other seals are VITON.
Mounting:
2
bolt flange - see interface
dimensions.
Weight:
4
lbs., 2 oz., shipped oil-filled.
NOTE:
To assure compliance with
National Fire Protection Association
Bulletin 31, “Installation of Oil
Burning Equipment”, fuel unit inlet
pressure should not exceed 3 psig.
Dimensions in inches, ( ) = cm