Page 4 - Condensate Pumps & Accessories

Scan this QR code to check
out the technical
data sheet
TECHNICAL SPECIFICATIONS
Max. flow rate
: 5.0
gph (19 l/h)
Max. discharge head
:
33
ft (10 m) (flow rate= 1gph (4l/h))
Max. pressure
:
46
ft (14 m) (flow rate= 0gph (0l/h))
Sound level at 3.3ft (1m)*
: 23
dBA
Mains supply
: 120
V ~ 60 Hz - 14 W
(1)
230
V ~ 50/60 Hz - 14 W
(2)
Detection levels
:
On : 23/32”, Off : 15/32’’, Alarm : 13/16’’
(
On :18mm, Off : 12mm, Alarm : 21mm)
Safety switch
:
NC 8A resistive - 250 V
Thermal protection (overheating)
: 194
°F (90°C) auto-reset
Protection
:
IP54
Safety standards
:
UL/CSA certified by Intertek
RoHS & WEEE directives
:
Compliant
mini condensate removal pump
Si-10
SO RELIABLE
Unmatched reliability
Low sound level
Energy saving
Easy to install
-
Thanks to high performances, high resistance to pollution created by general
environment.
-
Silent, whatever the air-conditioning unit and amount of condensates to be
removed.
INSTALLATION
Built-in three level detection unit. Can be connected at
the tank outlet or beside the air conditioner unit.
RECOMMENDED ACCESSORIES
*
according toEN ISO3744 (MeasuredatLNE lab,pumpoperatingwithwater,outofapplication)
for air-conditioners up to
5.6
tons (67 kBtu - 20 kW)
Wall mounted
Fan coils
Ceiling suspended units
Ducted units
4
Sauermann part # :
SI1000SIUS11 (1) or SI1000SIUS23(2)
PVC Tubing (ACC00105,ACC00150)
Self-sealing fittings to connect the
discharge tube into drain/waste
water pipe (ACC00205)
Rubber elbow 90° and “S” type
hose, for connection to the detection
unit inlet (ACC00208,ACC00209)
KIT CONTENTS
Piston pump, anti-vibration mounting bracket, plug in power cable with 2 safety
switch wires (5ft – 1.5 m), rubber elbow 90° Øint. 19/32’’ x 2’’3/8 (Øint. 15 x L
60
mm), vent tube Øint. 5/32’’ x L 2’’15/16 (Øint. 4 x L 75 mm).
PUMP
9
9
9
9
9
9
23
dBA
MANUFACTURER’S 2 YEAR WARRANTY
DISCHARGE HEAD
FLOW RATE