Background Image
Previous Page  109 / 124 Next Page
Information
Show Menu
Previous Page 109 / 124 Next Page
Page Background

LIQUID MANAGEMENT

LIQUID LEVEL GAUGES FOR RECEIVERS

MOUNTING BRACKET ASSEMBLIES

RECEIVER ACCESSORIES

Applications

Henry Technologies’ Liquid Level Gauges are designed for use on Horizontal

Liquid Receivers between 8-5/8” and 20” diameter. Mounting Flanges are

not included on most Receivers. Please contact Technical Support at 1-800-

627-5148 for application assistance.

Henry Technologies' Liquid Level Gauges are suitable for use with HFC and

HCFC refrigerants and their associated oils.

Technical Specifications

Maximum working pressure = 300 PSI (20.7 Bar)

Allowable operating temperature = -20°F to +250°F (-29°C to +121°C)

Installation - Notes

1. Liquid Level Gauges are to be installed horizontally.

2. Full instructions are given in the Product Instruction Sheet, included

with each Gauge.

Part No

Receiver

Diameter

Dimensions (inch)

A

B

C

S-9450

8-5/8

1.77

2.87

2.45

S-9451

10-3/4

1.77

2.87

2.45

S-9452

12-3/4

1.77

2.87

2.45

S-9453

14

1.77

2.87

2.45

S-9454

16

1.77

2.87

2.45

S-9455

18

1.77

2.87

2.45

S-9456

20

1.77

2.87

2.45

A

A

B

C

Part No

Dimensions (inch)

ØA

B

C

D

3-019-905

5.0

2.72

5.44

7.44

3-019-906

6.0

3.22

6.44

8.44

3-019-908

8-5/8

4.53

9.06

10.18

3-019-910

10-3/4

5.60

11.20

12.33

3-019-912

12-3/4

6.66

13.32

14.45

Applications

Henry Technologies Mounting Brackets are designed for use on vessels

between 5” and 12.75” diameter. Mounting hardware for the bracket is not

included.

Installation - Notes

1. Mounting brackets are designed for use on horizontal vessels only. Do

not use on vertically mounted vessels.

ROTALOCK SPUDS

B

C

D

Ø

A

Ø

A

Ø

B

C

Ø

A

Ø

B

C

FIG 1

FIG 2

Part No Fig

No

Thread

(inch)

Dimensions (inch)

ØA

ØB

C

2-009-037 1

1”-14

.497

.625

1.06

3-009-308 2 1-1/4” - 12

.875

1.125

1.94

2-009-046 1 1-3/4” - 12 1.125 1.375

1.72

Applications

Henry Technologies' Rotalock Spuds are available as an accessory for

applications where an industry standard Rotalock connection is needed.

Rotalock spuds are made of steel and can be welded in or brazed in based

on the application. Henry Technologies offers a full line of Rotalock Valves in

SAE Flare and ODS connections. See the Rotalock Valve section for details.

Installation - Notes

1. External threads must be protected from spatter on weld in

applications.

2. Ensure Rotalock fittings are cool and clean before installing Teflon seal

and Rotalock valves.

109