Henry Catalogue 2010 - page 98

Industrial & Commercial Refrigeration Products
800.96.HENRY
®
Approach °F
7
8
9
10
11
Max
No.
Circuits
12
Cat.
No.
Nom
Tons
MBH GPM PSI MBH GPM PSI MBH GPM PSI MBH GPM PSI MBH GPM PSI MBH GPM PSI
Single
EM005
5
30
7.5 0.7 45 11.2 1.2 60 14.9 2.1 72 17.9 3.0 85 21.2 4.2 99 24.7 5.6
EM010
10
-
-
-
70 17.4 1.9 90 22.4 3.0 124 30.9 5.5 148 36.9 7.7 170 42.9 10.1
EM015
15 125 31.1 4.4 158 39.4 7.0 187 46.6 9.6 220 54.8 13.2 -
-
-
-
-
-
EM020
20 160 39.8 3.3 208 51.8 5.4 252 62.8 7.7 293 73.0 10.3 336 83.8 13.4 380 94.8 16.9
EM025
25 203 50.5 5.8 244 60.8 8.3 290 72.2 11.5 332 82.7 14.9 -
-
-
-
-
-
EM030
30 245 61.0 6.2 294 73.2 8.8 350 87.2 12.2 398 99.2 15.7 -
-
-
-
-
-
EM010
10
-
-
-
70 17.4 1.9 90 22.4 3.1 121 30.2 5.4 140 34.9 7.1 155 38.7 8.6
Dual
EM015
15 115 28.6 3.7 141 35.1 5.5 167 41.6 7.6 194 48.3 10.1 222 55.3 13.1 252 62.8 16.7
EM020
20 152 37.8 3.0 198 49.3 4.9 245 61.0 7.3 286 71.3 9.8 327 81.5 12.7 370 92.3 16.0
EM025
25 203 50.5 5.8 244 60.8 8.3 290 72.2 11.5 332 82.7 14.9 -
-
-
-
-
-
EM030
30 237 59.0 5.8 287 71.5 8.4 340 84.7 11.5 390 97.2 15.0 -
-
-
-
-
-
EM035
35 230 57.3 3.2 310 77.2 5.6 385 95.9 8.4 445 110.9 11.1 505 125.9 14.0 -
-
-
Single
or
Dual
EM050
50 425 105.8 5.9 510 127.0 8.3 600 146.5 11.4 680 169.5 14.4 -
-
-
-
-
-
EM060
60 428 106.6 4.3 550 137.0 6.9 680 169.4 10.4 799 199.1 14.2 -
-
-
-
-
-
EM075
75 584 145.4 4.9 730 181.8 7.4 865 215.5 10.2 1004 250.2 13.6 -
-
-
-
-
-
EM090
90 650 161.8 4.1 830 206.7 6.6 1030 256.6 10.0 1200 299.0 13.4 -
-
-
-
-
-
EM100
100 778 193.7 4.4 994 247.6 7.1 1180 294.0 9.9 1370 341.4 13.2 -
-
-
-
-
-
EM125
125 943 234.8 5.7 1188 295.9 8.8 1428 355.8 12.5 1634 407.2 16.2 -
-
-
-
-
-
EM150
150 1084 269.9 4.7 1393 346.9 7.6 1720 428.5 11.4 2000 498.4 15.2 -
-
-
-
-
-
EM185
185 1417 352.8 7.0 1768 440.3 10.7 2090 520.7 14.7
-
-
-
-
-
-
-
-
-
EM225
225 1680 418.3 4.4 2130 530.5 6.9 2552 635.8 9.8 2966 739.2 13.0 3393 845.8 16.9
EM300
300 2284 568.7 6.7 2871 715.0 10.4 3401 847.3 14.4
-
-
-
-
-
-
-
-
-
C3
Capacity, GPM and Pressure Drop Data for 8°F Range R22
Catalog units presented above are designed for the listed ratings. Higher capacities may be possible with different baffle spacing's. Contact Factory.
The capacity data table above is based on R12 with water
range at 8°F and approach at 7-12°F.
Sizing
—To select the direct expansion chiller you must know:
1. Capacity at maximum load in thousands of BTU/HR (MBH)
[Capacity BTU/HR = GPM X RANGE X 500]
2. Water cooling range °F: inlet water temperature
minus
outlet water temperature.
3. Approach temperature °F: outlet water temperature
minus
refrigerant evaporating temperature.
The final selection may depend on the water side pressure drop
(psi), at the full GPM flow rate, being within acceptable limits.
See example below.
DUTY
SELECTION
Required Capacity: 5.85 T.R. x 12000 = 70.2 MBH
Range: (52-44) = 8°F
Entering water temperature: 52°F
Approach: (44-34) = 10°F
Leaving water temperature: 44°F
From above table, select EM010; maximum capacity
Refrigerant evaporating temperature: 34°F
72 MBH, requiring 17.9 GPM water with 3.0 PSI
Single Circuit
pressure drop: Model EM005-05060-1.
Nominal Ratings
in tons refrigeration (Nom Tons) are based on:
54°F entering water minus 44°F leaving water (10° range)
35°F evaporating temperature (9° approach)
100°F entering liquid refrigerant with 7°F suction superheat
0.00005 fouling factor
Limitations
Minimum evaporating temperature ……………………………32°F
Maximum water entering temperature ………………………..75°F
The listed water chillers are designed for the ranges and
approach temperatures in the tables. Consult factory for
selections at different conditions.
SELECTION PROCEDURE
CHILLERS
Direct Expansion