COMPONENTS
R32
ASME HORIZONTAL
All Pump-down Capacities are calculated @ 90% of receiver volume @ 90°F.
To convert to other refrigerants, consult technical service 800-627-5148.
Quotations on custom models available upon request.
MAXIMUM WORKING PRESSURE: 450 PSIG
.
Figure 3
Figure 2
Catalog No.
w/ Brackets
Fig.
No.
Dimensions in Inches
Pump Down Cap. (lbs)
ODS
Inlet
(G)
ODS
Outlet
(H)
Relief
NPT
(J)
Int. Volume
(ft^3) @
90%
Wt.
lbs
A
B
C
D
E
F
R22 R134A R404A R407C
S-8640V
2 8.625 36 4.63 18.00 4.63 9.00 68.7 69.7
59.5
66.8
7/8
7/8
1/2
0.95
65
S-8690V
10.75 36 6.50 18.00 6.50 11.00 105.3 106.9 91.3 102.4 1 1/8 1 1/8
1/2
1.45
115
2
S-8710V
10.75 60 6.50 30.00 9.00 11.00 180.1 182.8 156.2 175.1 1 1/8 1 1/8
1/2
2.48
166
2
S-8760V
12.75 60 8.00 30.00 11.00 13.00 255.8 259.5 221.7 248.7 1 3/8 1 3/8
1/2
3.53
218
2
S-8790
3
14
72 8.38 36.00 12.00 16.00 367.0 372.4 318.2 356.8 2 1/8 1 5/8
1/2
5.06
302
S-8810
16
60 8.88 30.00 14.00 18.00 400.0 405.8 346.7 388.9 2 5/8 2 1/8
1/2
5.52
366
3
S-8820
16
72 8.88 36.00 14.00 18.00 484.2 491.2 419.7 470.7 2 5/8 2 1/8
1/2
6.68
429
3
S-8830
16
84 8.88 42.00 14.00 18.00 568.3 576.6 492.7 552.5 3 1/8 2 1/8
1/2
7.84
492
3
S-8840
18
60 9.88 30.00 16.00 20.00 497.6 504.9 431.4 483.8 3 1/8 2 1/8
1/2
6.86
428
3
S-8850
18
72 9.88 36.00 16.00 20.00 603.5 612.4 523.2 586.8 3 1/8 2 1/8
1/2
8.32
499
3
S-8860
18
80 9.88 40.00 16.00 20.00 674.2 684.0 584.4 655.5 3 1/8 2 5/8
1/2
9.30
552
3
S-8870
20
72 10.50 36.00 18.00 22.00 726.4 737.1 629.8 706.3 3 1/8 2 5/8
1/2
10.02
555
3
Liquid Receivers