Henry Catalogue 2010 - page 42

Industrial & Commercial Refrigeration Products
800.96.HENRY
HENRY
®
V A L V E
H38
FILTER DRIERS
The drier is designed to function in both directions of
flow found in the reversible liquid line of heat pumps.
Internal check valves prevent release of collected
contaminants when the system switches from the
heating to cooling mode and back again.
A clean block from which all organic and volatile contaminants
are removed by the firing process
Uniformly effective with permeability and absorbency
throughout the molded core; micron filtration in depth will
remove and retain particles as small as 10 microns
High stability in a unit of good mechanical strength and
marked superiority in resistance to acid corrosion, moisture
incurred disintegration and fluid erosion; insoluble in organic
liquids and moisture
Removes dangerous acids
Spring cushioning at inlet end protects the block from rough
handling
Steel shell, maximum working pressure: 500 PSI (34.5 Bar)
Copper ODS connections
Features:
Heat Pump Filter-Drier Selection
Refrigerant R22 & R134a
Cat.
No.
Size
Conn.
Area Core
Filter
Dimensions in Inches
Wt.
Lbs.
Recommended
Tonnage
Water Cap. Drops
at 60 PPM
Flow Cap
@ 2 PSI
A
B
C
75°F
125°F
HP083-S
3/8
18
2.5
5.38
.47
1.22
1 thru 5
102
93
4.4
HP163-S
3/8
28
3.0
6.00
.17
1.76
1 thru 7
153
139
4.7
HP164-S
1/2
28
3.0
6.25
.53
1.76
1 thru 7
153
139
10.7
HP165-S
5/8
28
3.0
6.50
.66
1.84
1 thru 7
153
139
12.7