800.96.HENRY
Suitable for Ammonia
®
C12
Dimensions in Inches
“A” Nominal Dia.
“B”
8
2 3/4
10
3 1/2
12
3 3/4
14
4 3/4
16
6 1/2
18
7 3/8
20
7 1/2
24
8 1/2
30
10
36
10 1/2
42
13
48
14 1/2
Straight-through tube construction
with removable heads at both
ends; head passes with integral baffles to provide proper fluid velocity
with minimum pressure drop
Codes
: Construction to Section VIII of the ASME Code and CSA B-51,
B-52 and C-22.2 Codes; available with U symbol stamp (i.e. National
Board approval) when required
Working Pressures
: Shell side: 250 PSI
Tube side: 150 PSI
Heads
: Fabricated carbon steel with integrally welded pass divisions
Tubes
: 3⁄4" O.D. 16 gauge SA-179 seamless carbon steel
Tube Sheets
: Carbon steel SA 516-70 plate; tube holes are reamed
and double grooved
Connections
: Water–3" and smaller, MPT steel pipe;
connections 4" and larger, pipe stubs;
Ammonia–2" and smaller, MPT; 3 and larger, pipe stubs;
Freon–ODF as standard unless otherwise specified
Surge Drum
: Minimum 250 PSI working pressure, attached to liquid
chiller by suction risers welded to both shells; two risers are standard;
third riser supplied on larger units where required
Available Nominal Tube Lengths (N.T.L.)
:
6'6", 8', 10', 12', 14', 16', 18', 20', 22', 24', 26', 28', 30'
Available Surge Drum Nominal Diameters (S.D.)
:
6", 8", 10", 12", 14" 16", 20", 24", 30", 36", 42", 48"
All units are custom designed
according to the thermal duty and
your requirements