Industrial & Commercial Refrigeration Products
800.96.HENRY
®
C8
Incorporating CHIL-FLUX©
enhanced surface copper tubes for maximum heat transfer capability
Sizes 5 to 500
nominal tons refrigeration;
Working pressures
: Shell side 350 PSIG;
Tube side 125 PSIG
Straight through tube
construction and
removable heads
for tube cleaning.
Tubes roller expanded
into double
grooved tube sheets
Codes
: National Board of Boiler and
Pressure Vessel Inspectors. Designed and
manufactured in accordance with Section
VIII of the ASME Code and are available
with U or UM code symbol stamps.
Catalog
Number
Nom
Tons
Gas
In
Liq.Out
Water In/Out
Relief
Conn
Dimensions in Inches
Pump-down
Cap. Lbs
Ship
Wt.
Lbs.
A
B
C (FPT) Fig No.
D
F
G
H
J
CC005-06036-4
5
1 1/8
5/8
1 1/4
1
6 5/8
38 3/4
4 3/8 30
24
106
1/2
CC008-06048-4
8
1 3/8
7/8
1 1/4
1
6 5/8
50 3/4
4 3/8 42
32
125
1/2
CC011-08036-4
11
1 3/8
7/8
1 1/2
1
8 5/8
39 1/2
4 3/4 30
40
176
1/2
CC017-06048-4
17
1 5/8
1 1/8
2
1
8 5/8
51 1/2
4 3/4 42
54
205
1/2
CC021-08048-4
21
1 5/8
1 3/8
2
1
8 5/8
51 1/2
4 3/4 42
49
216
1/2
CC027-08072-2
27
2 1/8
1 3/8
2 1/2
2
8 5/8
75 1/2
4 3/4 66
77
270
1/2
CC032-08072-2
32
2 1/8
1 3/8
2 1/2
2
8 5/8
75 1/2
4 3/4 66
70
290
1/2
CC040-10072-2
40
2 5/8
1 5/8
3
2
10 3/4 76 3/4
6 1/2 64
119
420
1/2
CC050-10072-2
50
2 5/8
1 5/8
3
2
10 3/4 76 3/4
6 1/2 64
106
450
1/2
CC060-10096-2
60
2 5/8
1 5/8
3
2
10 3/4 100 3/4 6 1/2 88
158
515
1/2
CC075-10096-2
75
3 1/8
2 1/8
3
2
10 3/4 100 3/4 6 1/2 88
141
555
1/2
Fluid Type: Water
Refrigerant Type: R22
Fluid Inlet Temperature: 85°F
Fluid Outlet Temperature: 95°F
Condensing Temperature: 105°F
Standard
Reference
Model
Henry Equivalent
Heat
Exchanged
BTU/hr
Length
Inches
O.D.
Inches
Water
In/Out
Conn. In.
Refrigerant Connections Water
Flow
GPM
Water
Pressure
Drop, psi
Inlet
Outlet
HTHE-5
CC005-06024-410
76,500
24
6.625
1 NPT
1.125 ODS 0.625 ODS
15.4
2.1
HTHE-7
CC007-06030-410
111,000
30
6.625 1.25 NPT 1.375 ODS 0.875 ODS
22.3
4.0
HTHE-10
CC010-06030-410
147,000
30
6.625 1.25 NPT 1.375 ODS 0.875 ODS
29.6
4.2
HTHE-15
CC015-08030-410
222,000
30
8.625
2 NPT
1.625 ODS 1.125 ODS
44.7
1.8
HTHE-20
CC020-08048-210
303,000
48
8.625
2 NPT
1.625 ODS 1.125 ODS
61.0
0.9
HTHE-25
CC025-08048-210
346,500
48
8.625
2 NPT
2.125 ODS 1.375 ODS
69.7
0.8
HTHE-30
CC030-10048-210
435,000
48
10.75
2.5 NPT
2.125 ODS 1.375 ODS
87.6
0.9
HTHE-40
CC040-10060-210
603,000
60
10.75
3 NPT
2.125 ODS 1.375 ODS
121
1.9
HTHE-50
CC050-10060-210
786,000
60
10.75
3 NPT
2.625 ODS 1.625 ODS
158
1.8
HTHE-60
CC060-12060-210
904,500
60
12.75
3 NPT
2.625 ODS 1.625 ODS
182
1.9
HTHE-70
CC070-12060-210
1,054,500
60
12.75
4 NPT
3.125 ODS 2.125 ODS
212
1.9
HTHE-80
CC080-12060-210
1,230,000
60
12.75
4 NPT
3.125 ODS 2.125 ODS
248
1.9
HTHE-100
CC0100-12096-110
1,500,000
96
12.75
5 NPT
3.125 ODS 2.125 ODS
302
0.8
HTHE-125
CC0125-12096-110
1,875,000
96
12.75
5 NPT
3.625 ODS 2.125 ODS
377
0.9
Nominal tons rated on 14,000 btu/hr at 105°F condensing temperature with water inlet 85°F and outlet 95°F.
Pump Down Capacity based on R-22 at 90°F with condenser 80% full.
CONDENSERS
Marine Shell and Tube