Page 85 - Transformers Full Line

D
ONGAN
E
LECTRIC
M
ANUFACTURING
C
O
. • 2987
F
RANKLIN
TROIT
,
MI 48207
800.428.2626 • 313.567.8500 •
F
AX
313.567.8828 •
w.dongan.com
83
" % (
?
<% 3
,1 ;
,"
=
S (2 - 4 ,1 ,"
;
'
3
(2 -
%% &
Primary
Connections
Secondary
Connections
Pri.
Voltage
Connect
Incoming
Lines To:
Sec.
Voltage
Connect
Load
Lines To:
380
H1 & H3
24*
X1 & X3
416
H1 & H4
120
X1 & X4
480
H1 & H5
%% &
Primary
Connections
Secondary
Connections
Pri.
Voltage
Connect
Incoming
Lines To:
Sec.
Voltage
Connect
Load
Lines To:
220
H1 & H3
95
X1 & X3
380
H1 & H4
115
X1 & X4
400
H1 & H5
120
X1 & X5
416
H1 & H6
%% &
Primary
Connections
Secondary
Connections
Pri.
Voltage
Connect
Incoming
LinesTo:
Sec.
Voltage
Connect
Load
LinesTo:
380
H1&H3
110
X1&X3
400
H1&H3
115
X1&X3
416
H1&H4
115
X1&X4
440
H1&H4
120
X1&X4
460
H1&H4
115
X1&X3
480
H1&H4
120
X1&X3
575
H1&H5
120
X1&X4
%% &
Primary
Connections
Secondary
Connections
Pri.
Voltage
Connect
Incoming
Lines To:
Sec.
Voltage
Interconnect
Connect
Load
Lines To:
380
H1 & H2
110
X1 to X3
&
X2 to X4
X1 & X4
400
H1 & H2
115
X1 & X4
416
H1 & H2
120
X1 & X4
380
H1 & H2
220
X2 to X3
X1 & X4
400
H1 & H2
230
X1 & X4
416
H1 & H2
240
X1 & X4
416
H1 & H2
120/240
X2 to X3 X1 & X2/X3 & X4
"