Wholesalercat_APA_2012_LOW-complete - page 139

137
Type
Setting range
bar P
e
Differential
bar
Max. working pressure
bar P
e
Code number
Ambient temperature: -40 - 70 °C
CAS133
0
à
3.5
0.1
10
060-315066
CAS136
0
à
10
0.2
22
060-315166
CAS137
6
à
18
0.3
27
060-315266
CAS139
10
à
35
0.6
53
060-315366
CAS pressure switches for high pressure and strongly pulsating media
Ambient temperature: -25 - 70 °C
CAS143
1
à
10
0.2
à
0.6
120
060-316066
CAS145
4
à
40
0.8
à
2.4
120
060-316166
CAS147
6
à
60
1
à
3
120
060-316266
CAS Heavy-duty pressure switches with pipe thread connection
Contact type:
SPDT
Loads:
AC-1 (ohmic)
AC-3 (motor)
AC15 (inductive) 0.1 A 220V
Pressure connection:
G 1/4 A
Spare parts for CAS pressure switch
Description
Code numbers
Connector with nipple. Pipe thread ISO 228/1, G 3/8 connector, nipple and AL washer (10 mm ext. / 8 mm int. diam). for soldering onto
steel or copper tubing. Steel span of jaws: 22
017-436866
Connector with nipple. G 3/8 connector nipple and washer (10 mm ext. / 6.5 mm int. diam). For welding. Steel span of jaws: 22
017-422966
Reducer. G 3/8 x 7/16 - 20 UNF (1/4 flare) reduction with washer
017-420566
Adaptor G 3/8 A x 1/4 - 18 NPT with washer
060-333666
Nipple G 1/4 A x G 3/8 A
060-333266
Damping coil with G 3/8 connectors and 1.5 m copper capillary tube
060-104766
Armoured damping coil with 3/8 connectors and 1 m armoured capillary tube. Standard washers included.
060-333366
CAS differential pressure switch
Pressure connection: 2 x G ¼. Ambient temperature: -25 - 70 °C
Type
Setting range
bar P
e
Differential
bar
Max. working pressure
bar P
e
Code number
CAS155
0.2
à
2.5
0.1
0
à
8
060-313066
Nipple G 1/4 A x G 3/8A
Reducer
Connector w nipple
Adaptor
Damping coil
Damping coil,
armoured
1...,129,130,131,132,133,134,135,136,137,138 140,141,142,143,144,145,146,147,148,149,...172